Hello! Jiangxi Jianan Fire Science and Technology Co.

400-915-1190

Products and Services

Products & Services

  1. Home
  2. "
  3. Perfluorohexanone
  4. "
  5. Perfluorohexanone fire extinguishing equipment for power distribution cabinets

Perfluorohexanone fire extinguishing equipment for power distribution cabinets

全氟己酮配电柜灭火装置

Product Details

I. Principles of fire extinguishing
    It is mainly to extinguish the fire by removing most of the heat from the fire scene, i.e.: after the release of perfluorohexanone fire extinguishing agent, it forms a gaseous mixture with the carrier gas N2, which is very easy to absorb or consume a large amount of heat, so as to extinguish the flame temperature quickly and realize efficient fire extinguishing.

II. Main advantages
1, good environmental performance: green environmental protection gas;
2、High fire extinguishing efficiency: low fire extinguishing concentration can quickly extinguish the fire;
3. Safety in use: no cases of low toxicity have been observed;
4, good electrical insulation properties: ordinary wire and cable does not cause damage to the insulator;
5, fast cooling effect: fire extinguishing agent sprayed with a unique cooling effect;
6, extinguish the fire without residue: in the use of rapid evaporation, will not cause damage to precision instruments, antique paintings and calligraphy;
7, atmospheric storage and transportation without worry: liquid at room temperature, can be transported as ordinary goods, easy to fill, transportation and storage;
8, can extinguish electrical fires, solid surface fires, liquid fires and gas fires that can cut off the gas source before extinguishing.

III. Existing types and specifications
    按客户需求可定制。

IV. Main parameters
1、熔点:-108°C;
1、沸点:49°C
2、密度:1,6 g/cm3;
3、液体黏度:(0℃/25℃),Mpa•s:0.56/0.39;
4、绝缘性能(110Kv):3.8mA(标准值泄漏电流≤10mA);
5、非挥发性残留物%:≤0.01;
6、设计浓度%:3.5-5.5;
7、灭火喷放时间:一般防护区≤10s,通讯机房和电子计算机房等防护区 ≤8s;
8、额定增压压力: 
一级 2.5±0.1MPa 表压;二级 4.2±0.1MPa 表压。
9、灭火剂储存容器中的单位充装率: 
一级增压储存容器,不应大于1480(Kg/m3); 二级增压储存容器,不应大于1440(Kg/m3)。
10、氮气的含水量应小于0.006%;
11、灭火系统设计温度:20℃;
12、特殊场所灭火浓度设计:
(1)图书、档案、票据和文物资料库等防护区,灭火设计浓度10%。 
(2)油浸变压器室。带油开关的配电室和自备发电机房等防护区,灭火设计浓度9%。
(3)通讯机房和电子计算机房等防护区,灭火设计浓度8%。

V. Areas of application (places)
广泛应用于全区域或局部区域灭火系统及手提式灭火器,尤其适用于电子控制中心、计算机房、配电房、配电柜、风电机房、储能电站、高级精密仪器、博物馆、数据处理中心、舰船控制机房、新能源汽车锂电池、地铁车站、大型超市、公众密集场所等的防护等多种场合火灾防护。
不适用于下列场所物质火灾:
1、硝化纤维、硝酸钠等氧化剂或含氧化剂的化学制品火灾;
2、钾、镁、钠、钛、锆、铀等活泼金属火灾;
3、 氢化钾、氢化钠等金属氢化物火灾; 
4、过氧化氢、连胺等能自行分解的化学物质火灾;
5、可燃固体的深位火灾。

en_USEnglish