Hello! Jiangxi Jianan Fire Science and Technology Co.

Products and Services

Products & Services

  1. Home
  2. "
  3. IG541
  4. "
  5. IG541

IG541

IG541

Product Details

I. Principles of fire extinguishing

The IG541 Fire Suppression System reduces combustion temperatures by lowering the oxygen content to a level conducive to combustion. When an IG541 fire suppression system is vented into a room, it introduces the proper mixture of gases to allow people to breathe in an environment with reduced oxygen levels. In essence, it enhances the body's ability to absorb oxygen. Normal atmospheric air in a room contains approximately 21% of oxygen and less than 1% of carbon dioxide.

Most common combustibles will not burn when the oxygen content is reduced below 151 TP3T.The IG541 fire suppression system reduces the oxygen content to approximately 12.51 TP3T while increasing the carbon dioxide content to approximately 31 TP3T.The IG-541 effectively reduces the concentration of oxygen and prevents the combustion reaction from proceeding to extinguish the fire.

II. Advantages

Rapid fire suppression: Rapid suppression of fire by reducing oxygen concentration.

SAFETY: When used at the designed concentration, it is safe for humans, does not cause cardiac distress, and maintains arterial oxygen and mental performance even at low oxygen levels.

No Chemical Reaction: Unlike some chemical gaseous extinguishing agents, IG-541 does not react with fire to produce toxic or corrosive by-products.

Cost Effective: IG-541 is cost competitive with some chemicals and does not take up valuable floor space as cylinders can be placed away from protected areas.

Remote Storage: The IG-541 can be stored remotely up to 100 meters away from the protected area, meaning that a single cylinder bank can economically protect multiple areas.

 

Specification

Item

QMH15/80-JXJA

QMH15/90-JXJA

Design pressure (MPa)

17.2

Working Pressure(MPa)

15

Ambient temperature (℃)

0 to 50

Bottle volume L

80

90

Bottle filling capacity (20℃)m³

12

13.5

System operating voltage

220V AC, 24VDC

System startup method

Electrical automatic, electrical manual, mechanical emergency start

Outer diameter of fire extinguishing cylinder D(mm)

φ279

φ279/φ325

Height of fire extinguishing cylinder H(mm)

1578+73

1345+60

Gas mixture charge (m³)

12

13.5

Nominal diameter of container valve(mm)

15

Container valve outlet thread

M30×1.5

Safety relief pressure (MPa)

23±1.15

Fire extinguishing Concentration

Extinguish Class A solid surface fires

28.1%

Extinguish Class B liquid fires

33.8%

Design Concentration

Extinguish Class A solid surface fires

36.5%

Extinguish Class B liquid fires

43.9%

Design concentration in occupied workplaces

37.5~43%

 

4、Application places

 Electronic computer room, communication room, transformer room, electrical switchgear and distribution room, generator room, oil dipping tanks, drying equipment, paint spraying room, electrical instrumentation room, control center, library and archives, documentary collection, etc.

en_USEnglish