- Advantages: good environmental performance, good fire extinguishing effect, safe to use, good electrical insulation performance, cooling effect block, no residual fire extinguishing, atmospheric storage and transportation without worry, can extinguish electrical fires
- Fire extinguishing principle: mainly by removing most of the heat from the fire scene to extinguish the fire
- Hotline: 400-915-1190
Product Details
I. Principles of fire extinguishing
It is mainly to extinguish the fire by removing most of the heat from the fire scene, i.e.: after the release of perfluorohexanone fire extinguishing agent, it forms a gaseous mixture with the carrier gas N2, which is very easy to absorb or consume a large amount of heat, so as to extinguish the flame temperature quickly and realize efficient fire extinguishing.
II. Main advantages
1, good environmental performance: green environmental protection gas;
2、High fire extinguishing efficiency: low fire extinguishing concentration can quickly extinguish the fire;
3. Safety in use: no cases of low toxicity have been observed;
4, good electrical insulation properties: ordinary wire and cable does not cause damage to the insulator;
5, fast cooling effect: fire extinguishing agent sprayed with a unique cooling effect;
6, extinguish the fire without residue: in the use of rapid evaporation, will not cause damage to precision instruments, antique paintings and calligraphy;
7, atmospheric storage and transportation without worry: liquid at room temperature, can be transported as ordinary goods, easy to fill, transportation and storage;
8, can extinguish electrical fires, solid surface fires, liquid fires and gas fires that can cut off the gas source before extinguishing.
III. Existing types and specifications
Single bottle set (40/70/90/100/120/150/180)
Double bottle set (70*2/90*2/100*2/120*2/150*2)
IV. Technical parameters
Product model specification |
YF /2.5-N-Y |
Nominal working pressure(Mpa) |
2.5 |
Maximum working pressure(Mpa) |
3.2 |
injection time(S) |
≤10 |
Filling density(Kg/m³) |
≤1420 |
Operating Temperature Range |
-10~50℃ |
System fire extinguishing method |
be completely submerged |
System startup power |
24V,1.3A |
Safety relief device operating pressure(Mpa) |
4.5±0.225 |
V. Areas of application (places)
Suitable for computer rooms, archives, valuables warehouse, communication room and other small space protection area, several The combination of counter-type perfluorohexanone fire extinguishing equipment can also protect larger protected areas. When the building can not be set up special The bottle group room of the bottle group, or although there is a bottle group room, but the conveyance distance is far away, can not meet the requirements of the engineering design, or prevent the This device can be used when it is not convenient to install a system pipe network in the protection zone.