I. Principles of fire extinguishing
IG100 nitrogen fire extinguishing system adopts the principle of total flooding to reduce the oxygen concentration in the protected area from 21% to below 15%. When the oxygen concentration is lower than 15%, the fire will be suppressed due to the inability to maintain combustion.The amount of inert gas required to completely extinguish a fire is a design concentration based on room volume and fire hazard class. Once smoke and heat are detected, IG100 nitrogen stored in high pressure cylinders is automatically vented into the enclosed space through the dispensing piping and discharge nozzles within 60 seconds.
II. Main advantages
- Effectively extinguish fires caused by various combustible substances and flammable liquids.
- Clean without residue, no need to clean up after a fire
- Environmentally friendly, does not destroy the ozone layer, no greenhouse effect
- No damage to protected assets
- Safe and harmless to humans
- Internationally recognized, European approved and recognized by Malaysian authorities. Available in 80L and 140L cylinders with pressures of 200 and 300 bar.
Specification Item | QMH15/80-JXJA | QMH15/90-JXJA | ||
Design pressure (MPa) | 17.2 | |||
Working Pressure(MPa) | 15 | |||
Ambient temperature (℃) | 0 to 50 | |||
Bottle volume L | 80 | 90 | ||
Bottle filling capacity (20℃)m³ | 12 | 13.5 | ||
System operating voltage | 220V AC, 24VDC | |||
System startup method | Electrical automatic, electrical manual, mechanical emergency start | |||
Outer diameter of fire extinguishing cylinder D(mm) | φ279 | φ279/φ325 | ||
Height of fire extinguishing cylinder H(mm) | 1578+73 | 1345+60 | ||
Gas mixture charge (m³) | 12 | 13.5 | ||
Nominal diameter of container valve(mm) | 15 | |||
Container valve outlet thread | M30×1.5 | |||
Safety relief pressure (MPa) | 23±1.15 | |||
Fire extinguishing Concentration | Extinguish Class A solid surface fires | 28.1% | ||
Extinguish Class B liquid fires | 33.8% | |||
Design Concentration | Extinguish Class A solid surface fires | 36.5% | ||
Extinguish Class B liquid fires | 43.9% | |||
Design concentration in occupied workplaces | 37.5~43% |
4、Application places
Electronic computer room, communication room, transformer room, electrical switchgear and distribution room, generator room, oil dipping tanks, drying equipment, paint spraying room, electrical instrumentation room, control center, library and archives, collection of documentary materials, etc.